@@ -243,7 +243,7 @@ It is suggested to have seasonal mappings for some equipment. For instance, it m
243243
4. Wait up to *260 seconds* for the supply fan status feedback to turn off.
244244
5. Lock the supply fan on.
245245
6. Wait up to *260 seconds* for the supply fan status feedback to turn on.
246-
7. Repeat the following for $x\in\{100,95,90,85,80,75,70,65,60,55,50,45,40,35,30,25,20,15,10,5,0\}$
246+
7. Repeat the following for $x\in\\{100,95,90,85,80,75,70,65,60,55,50,45,40,35,30,25,20,15,10,5,0\\}$
247247
1. Lock the airflow damper to $x$ *percent*.
248248
2. Wait up to *260* seconds for the measured airflow damper position to be within *1%* of $x$.
249249
3. Measure the airflow *5 times* at *2 second* intervals, and record the averaged result.
@@ -263,4 +263,4 @@ It is suggested to have seasonal mappings for some equipment. For instance, it m
263263
21. Measure temperature at *10 second* intervals, and wait for the temperature graph to stabilize.
264264
22. Lock all DX cooling stages off.
265265
23. Measure temperature *26 times* at *10 second* intervals.
266-
24. Return all nodes to their default values (e.g, unlock points which were locked earlier in the test).
266+
24. Return all nodes to their default values (e.g, unlock points which were locked earlier in the test).